Inspection #: 736864
Inspection Type: Final Electrical
Inspector: N.Holland
Result: Correction
Comment: See Corrections Work is incomplete.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/12/2022TransferCorrect Below* Panel Update panel schedule
10/12/2022CorrectedCorrect Below* Front counterIs not a listed assembly to be plugged into the wall. Front counter will need to be wired to chapter 3 wiring methods.
10/12/2022TransferCorrect Below* Throughout MC cable needs to be supported so it is not lying on suspended ceiling.
10/12/2022TransferCorrect Below* Patient care areasAll branch circuits serving these spaces shall be provided with an effective ground fault current path. 2017 NEC 517.13 A This includes circuits that go to light switches as well as receptacles.