Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 736592
Inspection Type: Electrical Inspection
Inspector:
Result:
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/11/2022 Correct following Item  ServiceNeed intersystem bonding jumper
10/11/2022 Correct following Item  Main Disconnect GEC needs to be continuous to service. Bond both ends when traveling through metal raceway.
10/11/2022 Correct following Item  ServiceNeed posting of available fault current NEC 110.24
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS