Inspection #: 735784
Inspection Type: Electrical Inspection
Inspector: N.Holland
Result: Correction
Comment: See Corrections TAG# 39194

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/11/2022TransferCorrect following Item  ServiceNeed intersystem bonding jumper
10/11/2022TransferCorrect following Item  Main Disconnect GEC needs to be continuous to service. Bond both ends when traveling through metal raceway.
10/11/2022TransferCorrect following Item  ServiceNeed posting of available fault current NEC 110.24