Inspection #: 735667
Inspection Type: Final Electrical
Inspector: M.Green
Result: Cancel
Comment: Cancelled by Dave Elmore.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/5/2022TransferCorrect Below* RTU short circuit current rating.Units labelled with 65K AIC rating "WHEN PROTECTED BY CLASS J FUSES SIZED TO THE MOP. No class J fuses installed. What is the short circuit current rating of the units WITHOUT class J fuses? Are class J fuses required in all cases?
10/5/2022TransferCorrect Below* Available fault current at RTUs.440.10(B) requires available fault current to be labelled at units with date calculated. Plans specify RTU breakers to be 42K min rated.
10/5/2022TransferCorrect Below* RTU-9.Gas line violates 110.26 working clearances.
10/5/2022TransferCorrect Below* RTU-5.Service receptacle dead.
10/5/2022TransferCorrect Below* RTU-1Labelled 125A max OCPD. Breaker supplying unit in dist. panel "Service 2" is 200A.
10/5/2022TransferCorrect Below* RTU disconnects on units.At least (2) are 8ft above standing surface. Switches required to be readily accessible - no more than 6ft - 7in high.
10/5/2022TransferCorrect Below* RTU-3.Label indicates 158A min ckt. ampacity and 200A max OCPD. Breaker in panel "Mech 4" is 125A.
10/5/2022TransferCorrect Below* RTU-3.Drawings do not seem to indicate source of supply. RTU-3 circuit originates in panel "Mech 4."
10/5/2022TransferCorrect Below* Drawings on site.Drawings show (9) rooftop units. Alternates shown on drawings are confusing. Only units 1, 3, 5, and 9 have been replaced. Is this the minimum required by the drawings? Engineer may have to clarify.
10/5/2022TransferCorrect Below* Drawings on site.Drawings not stamped approved by MOA Plan Review.