| Date | Status | Code | Description | Ref | Location | Comments |
| 10/5/2022 | Transfer | Correct Below | * | | RTU short circuit current rating. | Units labelled with 65K AIC rating "WHEN PROTECTED BY CLASS J FUSES SIZED TO THE MOP. No class J fuses installed. What is the short circuit current rating of the units WITHOUT class J fuses? Are class J fuses required in all cases? |
| 10/5/2022 | Transfer | Correct Below | * | | Available fault current at RTUs. | 440.10(B) requires available fault current to be labelled at units with date calculated. Plans specify RTU breakers to be 42K min rated. |
| 10/5/2022 | Transfer | Correct Below | * | | RTU-9. | Gas line violates 110.26 working clearances. |
| 10/5/2022 | Transfer | Correct Below | * | | RTU-5. | Service receptacle dead. |
| 10/5/2022 | Transfer | Correct Below | * | | RTU-1 | Labelled 125A max OCPD. Breaker supplying unit in dist. panel "Service 2" is 200A. |
| 10/5/2022 | Transfer | Correct Below | * | | RTU disconnects on units. | At least (2) are 8ft above standing surface. Switches required to be readily accessible - no more than 6ft - 7in high. |
| 10/5/2022 | Transfer | Correct Below | * | | RTU-3. | Label indicates 158A min ckt. ampacity and 200A max OCPD. Breaker in panel "Mech 4" is 125A. |
| 10/5/2022 | Transfer | Correct Below | * | | RTU-3. | Drawings do not seem to indicate source of supply. RTU-3 circuit originates in panel "Mech 4." |
| 10/5/2022 | Transfer | Correct Below | * | | Drawings on site. | Drawings show (9) rooftop units. Alternates shown on drawings are confusing. Only units 1, 3, 5, and 9 have been replaced. Is this the minimum required by the drawings? Engineer may have to clarify. |
| 10/5/2022 | Transfer | Correct Below | * | | Drawings on site. | Drawings not stamped approved by MOA Plan Review. |