Inspection #: 734946
Inspection Type: Final Electrical
Inspector: M.Green
Result: Cancel
Comment: Cancelled by Jaimey.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/26/2022TransferCorrect Below* Special permission item for (2) services on (1) building.Existing south end service requires new, main service disconnect / OCPD. New service OCPD to be shunt-trip type breaker with shunt trip actuator to be installed by Little Caesar's service. NOTE: TIMELINE FOR COMPLETION REQUIRED BY 10/25/2022.
9/26/2022TransferCorrect Below* Special permission item for (2) services on (1) building.Little Caesar's service OCPD required to be replaced with shunt-trip type breaker and shunt trip actuator installed by south end service. NOTE: TIMELINE FOR COMPLETION REQUIRED BY 10/25/2022.
9/26/2022TransferCorrect Below* Special permission item for (2) services on (1) building.Mall wiring is currently disconnected in Little Caesar"s soffit. Reconnect those soffit lights to Little Caesar"s and reconnect Silk restaurant soffit lights to Mall house panel. NOTE: COMPLETE BY 10/25/2022 AND REQUEST REINSPECTION.
9/26/2022TransferCorrect Below* Special permission item for (2) services on (1) building.NEC 230.2(E) requires placarding with all specifics detailed in that section. NOTE: THERE IS TEMPORARY PLACCARDING THAT DOES NOT MEET THE SPECIFICS OF 230.2(E). CORRECT THIS BY 10/25/2022 AND REQUEST REINSPECTION.