| Date | Status | Code | Description | Ref | Location | Comments |
| 9/26/2022 | Corrected | Correct Below | * | | Lift station. | 1. Engineer needs to specify that this is a grey water lift station if not to be regarded as a hazardous location. 2. Receptacle under lid required to be GFCI protected. GFCI device to be readily accessible. NOTE: COMPLETE BY 10/25/2022 AND REQUEST REINSPECTION. |
| 9/26/2022 | Corrected | Correct Below | * | | Kitchen RTU. | 1. Gas piping violates 110.26 working clearance. 2. Label unit to match breaker designation. NOTE: COMPLETE BY 10/25/2022 AND REQUEST REINSPECTION. |
| 9/26/2022 | Transfer | Correct Below | * | | Special permission item for (2) services on (1) building. | Existing south end service requires new, main service disconnect / OCPD. New service OCPD to be shunt-trip type breaker with shunt trip actuator to be installed by Little Caesar's service. NOTE: TIMELINE FOR COMPLETION REQUIRED BY 10/25/2022. |
| 9/26/2022 | Transfer | Correct Below | * | | Special permission item for (2) services on (1) building. | Little Caesar's service OCPD required to be replaced with shunt-trip type breaker and shunt trip actuator installed by south end service. NOTE: TIMELINE FOR COMPLETION REQUIRED BY 10/25/2022. |
| 9/26/2022 | Transfer | Correct Below | * | | Special permission item for (2) services on (1) building. | Mall wiring is currently disconnected in Little Caesar"s soffit. Reconnect those soffit lights to Little Caesar"s and reconnect Silk restaurant soffit lights to Mall house panel. NOTE: COMPLETE BY 10/25/2022 AND REQUEST REINSPECTION. |
| 9/26/2022 | Transfer | Correct Below | * | | Special permission item for (2) services on (1) building. | NEC 230.2(E) requires placarding with all specifics detailed in that section. NOTE: THERE IS TEMPORARY PLACCARDING THAT DOES NOT MEET THE SPECIFICS OF 230.2(E). CORRECT THIS BY 10/25/2022 AND REQUEST REINSPECTION. |