Inspection #: 734215
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Contact Tom 907-841-4020 Requested by: Jodi Curry 9079529355 Jodi@ntsalaska.com | | Some items from 9/26/2022 inspection corrected. Engineer has provided a letter stating that the lift station is grey water only and does not constitute a hazardous location. Other items remain to be corrected. Corrections remaining require resolution by the dates specified. Call if questions.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/26/2022CorrectedCorrect Below* Lift station.1. Engineer needs to specify that this is a grey water lift station if not to be regarded as a hazardous location. 2. Receptacle under lid required to be GFCI protected. GFCI device to be readily accessible. NOTE: COMPLETE BY 10/25/2022 AND REQUEST REINSPECTION.
9/26/2022CorrectedCorrect Below* Kitchen RTU.1. Gas piping violates 110.26 working clearance. 2. Label unit to match breaker designation. NOTE: COMPLETE BY 10/25/2022 AND REQUEST REINSPECTION.
9/26/2022TransferCorrect Below* Special permission item for (2) services on (1) building.Existing south end service requires new, main service disconnect / OCPD. New service OCPD to be shunt-trip type breaker with shunt trip actuator to be installed by Little Caesar's service. NOTE: TIMELINE FOR COMPLETION REQUIRED BY 10/25/2022.
9/26/2022TransferCorrect Below* Special permission item for (2) services on (1) building.Little Caesar's service OCPD required to be replaced with shunt-trip type breaker and shunt trip actuator installed by south end service. NOTE: TIMELINE FOR COMPLETION REQUIRED BY 10/25/2022.
9/26/2022TransferCorrect Below* Special permission item for (2) services on (1) building.Mall wiring is currently disconnected in Little Caesar"s soffit. Reconnect those soffit lights to Little Caesar"s and reconnect Silk restaurant soffit lights to Mall house panel. NOTE: COMPLETE BY 10/25/2022 AND REQUEST REINSPECTION.
9/26/2022TransferCorrect Below* Special permission item for (2) services on (1) building.NEC 230.2(E) requires placarding with all specifics detailed in that section. NOTE: THERE IS TEMPORARY PLACCARDING THAT DOES NOT MEET THE SPECIFICS OF 230.2(E). CORRECT THIS BY 10/25/2022 AND REQUEST REINSPECTION.