Inspection #: 732970
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: Inspection for lounge, bar, kitchen, tools/maintenance. See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/14/2022TransferCorrect Below* Tools and maintenanceHeaters incomplete. Thermostat low voltage wiring not separate from power wiring. Maintain separation from power wiring to use class 2 wiring method, or class 2 system must be installed in a chapter 3 method approved for the location.
10/14/2022TransferCorrect Below* Lounge equipmentRequired to be installed for inspection. Equipment ID's 9-16
10/14/2022TransferCorrect Below* "Cloud lights"See 411.6 (C). Required to be installed minimum of 7' above finished floor unless specifically listed for lower installation.
10/14/2022TransferCorrect Below* Ice makerInstall instructions do not appear to specifically allow for cord connection. Instructions recommend to not connect to GFCI protected circuit. Hard wire connection with approved disconnect per 422.31 as required.
10/14/2022TransferCorrect Below* Kitchen equipment-dish washer, oven/steamer.Do not appear to have third party listing and ratings labeled on equipment.
9/7/2022TransferCorrect Below* ATO / BCOOffice furniture not installed at this time.