Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 732759
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Contact Tom 907-841-4020 Requested by: Jodi Curry 9079529355 Jodi@ntsalaska.com | | Corrections items have timeline of 10/25/2022. See below.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/26/2022TransferCorrect Below* Lift station.1. Engineer needs to specify that this is a grey water lift station if not to be regarded as a hazardous location. 2. Receptacle under lid required to be GFCI protected. GFCI device to be readily accessible. NOTE: COMPLETE BY 10/25/2022 AND REQUEST REINSPECTION.
9/26/2022TransferCorrect Below* Kitchen RTU.1. Gas piping violates 110.26 working clearance. 2. Label unit to match breaker designation. NOTE: COMPLETE BY 10/25/2022 AND REQUEST REINSPECTION.
9/26/2022TransferCorrect Below* Special permission item for (2) services on (1) building.Existing south end service requires new, main service disconnect / OCPD. New service OCPD to be shunt-trip type breaker with shunt trip actuator to be installed by Little Caesar's service. NOTE: TIMELINE FOR COMPLETION REQUIRED BY 10/25/2022.
9/26/2022TransferCorrect Below* Special permission item for (2) services on (1) building.Little Caesar's service OCPD required to be replaced with shunt-trip type breaker and shunt trip actuator installed by south end service. NOTE: TIMELINE FOR COMPLETION REQUIRED BY 10/25/2022.
9/26/2022TransferCorrect Below* Special permission item for (2) services on (1) building.Mall wiring is currently disconnected in Little Caesar"s soffit. Reconnect those soffit lights to Little Caesar"s and reconnect Silk restaurant soffit lights to Mall house panel. NOTE: COMPLETE BY 10/25/2022 AND REQUEST REINSPECTION.
9/26/2022TransferCorrect Below* Special permission item for (2) services on (1) building.NEC 230.2(E) requires placarding with all specifics detailed in that section. NOTE: THERE IS TEMPORARY PLACCARDING THAT DOES NOT MEET THE SPECIFICS OF 230.2(E). CORRECT THIS BY 10/25/2022 AND REQUEST REINSPECTION.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS