Inspection #: 731977
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Correction
Comment: some corrections made- no change to cco date

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/9/2022TransferCorrect Below* Lift Station1. Engineer needs to specify that this is a grey water lift station if not to be regarded as hazardous location. 2. Receptacle under lid required to be GFCI protected. GFCI device to be readily accessible.
9/9/2022CorrectedCorrect Below* EBCO dough divider.May require attachment plug for cord connection.
9/9/2022CorrectedCorrect Below* Stephan Hameln dough mixer.Installation requires 35A slow-blow fuses. May require attachment plug for cord connection.
9/9/2022CorrectedCorrect Below* MAUNeeds disconnect.
9/9/2022TransferCorrect Below* Kitchen RTU.1. Gas piping violates 110.26 working clearances. 2. Label unit to match breaker designation.
9/9/2022CorrectedCorrect Below* Corporate office RTU.1. Requires disconnect. 2. Label to correspond with breaker designation.
8/29/2022CorrectedCorrect Below*  additional items may be present- panel schedules not provided and not all receiving devices/wiring/panel makeup has been completed
8/29/2022TransferCorrect Below*  need access to rooftop
8/29/2022TransferCorrect Below*  Special permission terms for new service are required to be met- shunt trips at each service location, placarding of other service location, additional disconnect at south service, soffit lighting on Little Caesars service etc. UPDATE TO THIS INSPECTION COMMENT: 1. PLACARDING DENOTING (2) SERVICES IS REQUIRED TO CONFORM TO 230.2(E). 2. MALL WIRING IN LITTLE CAESAR'S SOFFIT NEEDS TO BE REMOVED. 3. SHUNT TRIPS AT BOTH SERVICES AND NEW SOUTH SERVICE MAIN DISCONNECT DATE FOR COMPLETION TO BE SET AT REINSPECTION ON OR BEFORE 9/23/2022.