Inspection #: 730345
Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: Contact Tom 907-841-4020 Requested by: JODI CURRY 907-952-9355 Jodi@ntsalaska.com | | Conditional electrical final approved until 9/23/2022. Correct items below and request reinspection.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/9/2022TransferCorrect Below* Lift Station1. Engineer needs to specify that this is a grey water lift station if not to be regarded as hazardous location. 2. Receptacle under lid required to be GFCI protected. GFCI device to be readily accessible.
9/9/2022TransferCorrect Below* EBCO dough divider.May require attachment plug for cord connection.
9/9/2022TransferCorrect Below* Stephan Hameln dough mixer.Installation requires 35A slow-blow fuses. May require attachment plug for cord connection.
9/9/2022TransferCorrect Below* MAUNeeds disconnect.
9/9/2022TransferCorrect Below* Kitchen RTU.1. Gas piping violates 110.26 working clearances. 2. Label unit to match breaker designation. 3. Service receptacle not type WR.
9/9/2022TransferCorrect Below* Corporate office RTU.1. Requires disconnect. 2. Label to correspond with breaker designation.
8/29/2022TransferCorrect Below*  additional items may be present- panel schedules not provided and not all receiving devices/wiring/panel makeup has been completed
8/29/2022CorrectedCorrect Below*  disconnects required for hardwired appliances
8/29/2022TransferCorrect Below*  need access to rooftop
8/29/2022CorrectedCorrect Below*  hood controller incomplete
8/29/2022CorrectedCorrect Below*  panel schedules and bundling required at panels
8/29/2022CorrectedCorrect Below*  ground fault protection, breakers locks and warning labels required for heat trace circuits
8/29/2022CorrectedCorrect Below*  receiving area not complete-
8/29/2022CorrectedCorrect Below*  receptacles miswired at POS and office
8/29/2022CorrectedCorrect Below*  some emergency lighting units and remote heads are not functioning properly
8/29/2022CorrectedCorrect Below*  gfci protection required for all kitchen receptacles per NEC 210.8B
8/29/2022CorrectedCorrect Below*  sign permit required for new Little Caesar's sign
8/29/2022TransferCorrect Below*  Special permission terms for new service are required to be met- shunt trips at each service location, placarding of other service location, additional disconnect at south service, soffit lighting on Little Caesars service etc. UPDATE TO THIS INSPECTION COMMENT: 1. PLACARDING DENOTING (2) SERVICES IS REQUIRED TO CONFORM TO 230.2(E). 2. MALL WIRING IN LITTLE CAESAR'S SOFFIT NEEDS TO BE REMOVED. 3. SHUNT TRIPS AT BOTH SERVICES AND NEW SOUTH SERVICE MAIN DISCONNECT DATE FOR COMPLETION TO BE SET AT REINSPECTION ON OR BEFORE 9/23/2022.