Inspection #: 729456
Inspection Type: Mechanical Inspection
Inspector: R.Larson
Result: Correction
Comment: Rest of RTU replacement inspected and Approved. See correction. NOTES: a) Labeled incorrectly as RTU-2 on electric service shutoff. b) Life/safety issue

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/16/2022TransferMechCommentsSee commentsSee comments belowRTU roof top'18 IMC 304.11 Guards; Guards shall be provided where various components that require service are located within 10 feet of a roof edge or open side of a walking surface and such edge or open side is located more than 30 inches above the floor, roof, or grade below. The guard shall extend not less than 30 inches beyond each end of components that require service. The top of the guard shall be located not less than 42 inches above the elevated surface adjacent to the guard. The guard shall be constructed so as to prevent the passage of a 21 inch diameter sphere and shall with the loading requirements for guards specified in the International Building Code.