| Date | Status | Code | Description | Ref | Location | Comments |
| 7/29/2022 | Transfer | Correct service item below | * | | (3) of (3) written, special permissions for non-standard service configuration. | 3. CEA WAIVER TO PERMIT ERICCSON 400A, 3-PHASE COMBO CT / SERVICE DISCONNECT. Currently known CEA identified deficiencies: 1. Equipment will not physically accept (2) 4in service lateral conduits. 2. Utility compartment / chase not permitted to be behind another cover. 3. CT compartment does not meet CEA size requirements. 4. CEA believes that line crew will have to remove service OCPD to pull in service lateral. |
| 7/29/2022 | Transfer | Correct service item below | * | | (2) of (3) written, special permissions for non-standard service configuration. | 2. CEA WAIVER PERMITTING 2ND SERVICE TO A SINGLE BUILDING THAT DOES NOT MEET CEA REQUIREMENTS FOR A 2ND SERVICE. |
| 7/29/2022 | Transfer | Correct service item below | * | | (1) of (3) written, special permissions for non-standard service configuration. | 1. ALTERNATE MEANS AND METHODS FROM MOA AND SIGNED BY THE BUILDING OFFICIAL.. Engineer has designed a 2nd service on a multi-tenant building that NEC does not normally permit to have a second service. |
| 7/29/2022 | Transfer | Correct service item below | * | | Grounding electrode conductor to water line. | GEC connection is currently made above a T-bar grid ceiling in a neighboring TI space. GEC connections to water line electrodes are required to be made within 5ft of water pipe entrance into the building. |
| 7/29/2022 | Transfer | Correct service item below | * | | Service raceway. | NEC requires a minimum 1/0 CU bonding jumper from service raceway to service enclosure. |
| 7/29/2022 | Transfer | Correct service item below | * | | Service. | Main grounding electrode conductor to water line needs to terminate directly on the neutral bus. |
| 7/18/2022 | Transfer | Correct service item below | * | | provide documentation "change order or alternate means" allowing for 2nd service to building and provide CEA approval for 2nd service per 302.4 of CEAs Electrical Service Requirements. | |