Inspection #: 722939
Inspection Type: Fire Sprinkler Rough-In
Inspector: D.Meneses
Result: Approved
Comment: Please call Trevor Crow 30 mins prior to arrival 9072232437 Requested by: Trevor Crow 19072232437 tcrow@yukonfire.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/17/2022 FireSprinkRoughOther1Fire Sprinkler Rough ApprovedFire Sprinkler Rough Approved  Items corrected from last report, system is okay to proceed.
7/13/2022 FireSprinkRough1Correction(s) #1Correct the following item(s): Required Special Inspection not completed for post installed concrete anchors per the requirements of 2018 IBC Section 1704, 1705.3 and Table 1705.3 #4.  