Inspection #: 722637
Inspection Type: Fire Sprinkler Bracing Final
Inspector: D.Meneses
Result: Approved
Comment: Please call Trevor Crow 30 mins prior to arrival 9072232437 Requested by: Trevor Crow 19072232437 tcrow@yukonfire.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/17/2022 FireSprkBracing1Approved - Fire Sprinkler BracingApproved fire sprinkler system bracing All corrections made from last report, okay to proceed.
7/13/2022 FireSprkBracing4Correction(s) #3<div>Correct the following item(s):</div><div><br></div> Re-inspection required after special inspection is completed and observation of attachments can be made.
7/13/2022 FireSprkBracing2Correction(s) #1<div>Correct the following item(s):</div><div><br></div> Sheet rock installed before inspections.&nbsp; &nbsp;Remove all sheetrock so proper inspection can be done of hangers and bracing for post installed concrete anchors.&nbsp;
7/13/2022 FireSprkBracing3Correction(s) #2<div>Correct the following item(s):</div><div><br></div> Required Special Inspection not completed for post installed concrete anchors per the requirements of 2018 IBC Section 1704, 1705.3 and Table 1705.3 #4.&nbsp; &nbsp;Pay Fine of $425.00 before final, for failure to perform required special inspection per AMC 23.10 Table 3-O #2.