Inspection #: 721866
Inspection Type: Plumbing Rough
Inspector: Y.Dovba
Result: Correction
Comment: Partial Plumbing Approved, Underfloor dwv rough-in and tests Approved, per plans M223. Kitchen and lounge area: Acid piping serving floor sinks, grease interceptor and clean-outs. Overhead recirculation piping tested and approved. NOTE: Per 2018 UPC section 707.4 provide clean-outs on upper terminals on vent piping above floor kitchen wall. Clean-outs will be inspected at final.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/21/2022TransferPlumbRgh14CommentsSee Inspectors CommentsUnderfloor Acid waste kitchen piping.Per 2018 UPC section 707.4 install clean-outs at upper terminals above the floor at kitchen equipment wall. NOTE: this correction can be inspected at final.