| Date | Status | Code | Description | Ref | Location | Comments |
| 6/29/2022 | | Correct Below | * | | 3rd floor VAV boxes. | Label indicates a max. current of 16A. Drawings show a 15A, 2-pole breaker. 15A OCPD installed. Engineer needs to investigate and change dwg. |
| 6/29/2022 | | Correct Below | * | | Refrigerant lines. | Violate 110.26(E) dedicated space above MDP and possibly other panels. |
| 6/29/2022 | | Correct Below | * | | AC units indoor and outdoor. | Label disconnects. |