Inspection #: 720788
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Remainder of electrical final. Please call Trevor Naylor for inspection. 907 355 3060 Requested by: Mike Casey 1907351968 mcasey@alcanelectric.com | | Electrical final inspection for all remodel areas on (3) floors.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
11/16/2022 Correct Below* 3rd floor office area.Some receptacles not type TR.
11/16/2022TransferCorrect Below* 1st floor ceiling in front of Pharmacy counters.Was not rough inspected.
11/16/2022TransferCorrect Below* 3rd floor offices.Electric raising and lowering tables not listed.
11/16/2022TransferCorrect Below* 3rd floor office area remodel.Drawings need the following changes: 1. Room numbers need to be changed to reflect actual configuration. 2. Show actual work done. Work not being done needs to be removed from plans.
11/16/2022TransferCorrect Below* 2nd floor Dental Reception area.Work consists of new Reception soffit with recessed lights, new reception desk pony wall receptacles, LED retrofit kits in 2 x 2 troffers. Please provide electrical rough inspections.
11/16/2022TransferCorrect Below* 1st floor Pharmacy soffits by motorized shutters at counters.Drivers at canless recessed lights need to be secured to structure.
6/29/2022TransferCorrect Below* Panel.Post final finished panel schedules. More detail. Floor plan posted needs to be larger.
6/29/2022CorrectedCorrect Below* Counter motorized shutters.Not complete.
6/29/2022CorrectedCorrect Below* Medical refrigerator receptacles within 6ft of sink.Require GFCI protection.
6/29/2022CorrectedCorrect Below* Consultation 106 and Dir Office 107.Require tamper resistant receptacles required.