Inspection #: 720023
Inspection Type: Final Mechanical
Inspector: K.Hanson
Result: Correction
Comment: Partial Mechanical Final - Approved To include the install of RTU-1, 3, 5 & 9 w/ related curb adapters, see corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/12/2022TransferMechFinal1 Previous inspection items have not been correctedGas regulatorsAs per 2018 IFGC 410.2 notes 5 & 6, test tees (2-each) required per regulator.
9/12/2022TransferMechFinal1 Previous inspection items have not been correctedGas regulatorsVent to point downward (typical), install guide not provided, add 90.