| Date | Status | Code | Description | Ref | Location | Comments |
| 8/14/2023 | Transfer | PlumbFinal | Comments | See Inspector Comments | Gas meter | As per 2018 IFGC 301.12 & 407.2 flex required to serve piping due to seismic forces & undue stress/strain on piping from uneven settling of meter/building. |
| 8/14/2023 | Transfer | PlumbFinal | Comments | See Inspector Comments | Rooftop gas piping | Adequately support rooftop "Metraflexes", support rooftop & meter gas piping per 2018 IFGC table 415.1 |
| 8/14/2023 | Transfer | PlumbFinal | Comments | See Inspector Comments | Rooftop gas regulators | As per local amendment to the 2018 IFGC 410.6, gas regulators shall be 2' above roof unless otherwise specified by manufacturer. |
| 8/14/2023 | Transfer | PlumbFinal | Comments | See Inspector Comments | Rooftop regulator gas piping | As per 2018 IFGC 410.2, all related unions, test tees & isolation valves shall be installed. |