Inspection #: 719835
Inspection Type: Final Plumbing
Inspector: K.Hanson
Result: Correction
Comment: All else OK regarding rooftop gas piping, see corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/14/2023TransferPlumbFinalCommentsSee Inspector CommentsGas meterAs per 2018 IFGC 301.12 & 407.2 flex required to serve piping due to seismic forces & undue stress/strain on piping from uneven settling of meter/building.
8/14/2023TransferPlumbFinalCommentsSee Inspector CommentsRooftop gas pipingAdequately support rooftop "Metraflexes", support rooftop & meter gas piping per 2018 IFGC table 415.1
8/14/2023TransferPlumbFinalCommentsSee Inspector CommentsRooftop gas regulatorsAs per local amendment to the 2018 IFGC 410.6, gas regulators shall be 2' above roof unless otherwise specified by manufacturer.
8/14/2023TransferPlumbFinalCommentsSee Inspector CommentsRooftop regulator gas pipingAs per 2018 IFGC 410.2, all related unions, test tees & isolation valves shall be installed.