Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: Please call Gene 30 minutes before (907)301-3720 Thanks Requested by: Scott Anderson (907)229-5968 sanderson@encoreak.com | | Conditional electrical final approved to set up until 6/1/2022.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/25/2022TransferCorrect Below* Branch circuit OCPD protection.240.24(B) requires that each occupant have ready access to ALL OCPDs protecting that occupancy. 240.24(B)(2) gives relief from this requirement only for hotel guest rooms. THE CURRENT BRANCH CIRCUIT OCPD ACCESS ARRANGEMENT IS NOT NEC COMPLIANT. THE TENNANT IS REQUIRED TO DEMONSTRATE KEY ACCESS TO THE COMMON ELECTRICAL ROOM AND HAVE A LETTER FROM BUILDING MANAGEMENT STATING THAT THE TENNANT WILL HAVE A KEY.
5/25/2022TransferCorrect Below* Provider offices.Meet the definition of "business office" at 406.12(5). Tamper resistant receptacles required.