Date | Status | Code | Description | Ref | Location | Comments |
5/11/2022 | Transfer | Correct Below | * | | Microturbine. | Need to inspect. Will need to see CEA written acceptance of alternate power source. |
5/11/2022 | Transfer | Correct Below | * | | Rooftop units, rooftop other. | Need to inspect. |
5/11/2022 | Transfer | Correct Below | * | | Site lighting. | Will need to inspect. |
5/11/2022 | Transfer | Correct Below | * | | Kitchen | Will need to see appliances to check for listings, etc. |
5/11/2022 | Transfer | Correct Below | * | | Back of house mech room. | (2) circ pump disconnects have Class 2 wiring inside. |
5/11/2022 | Transfer | Correct Below | * | | Back of house Pantry 157. | Walk-in cooler not installed. |
5/11/2022 | Transfer | Correct Below | * | | Motorized shades. | No apparent listing label. Do not use until listing verified. |
5/11/2022 | Transfer | Correct Below | * | | Guest room AC units. | Need 15A breakers |
5/11/2022 | Transfer | Correct Below | * | | Various guest rooms and conference rooms. | 120V motorized window shades do not appear to be listed.
Do not use until listing can be verified or until listed units can be installed. |
5/11/2022 | Transfer | Correct Below | * | | Guest room AC units floors 1 through 3. | Labelled to require 15A OCPD. |