Inspection #: 713407
Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: Remaining inspection for CCO w/ occupancy Requested by: Tim Gorham 3506496 tgorham@alcanelectric.com | | Conditional electrical final approved for occupancy until 5/30/2022. Items remaining will be listed in corrections below.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/11/2022TransferCorrect Below* Microturbine.Need to inspect. Will need to see CEA written acceptance of alternate power source.
5/11/2022TransferCorrect Below* Rooftop units, rooftop other. Need to inspect.
5/11/2022TransferCorrect Below* Site lighting.Will need to inspect.
5/11/2022TransferCorrect Below* KitchenWill need to see appliances to check for listings, etc.
5/11/2022TransferCorrect Below* Back of house mech room.(2) circ pump disconnects have Class 2 wiring inside.
5/11/2022TransferCorrect Below* Back of house Pantry 157.Walk-in cooler not installed.
5/11/2022TransferCorrect Below* Motorized shades.No apparent listing label. Do not use until listing verified.
5/11/2022TransferCorrect Below* Guest room AC units.Need 15A breakers
5/11/2022TransferCorrect Below* Various guest rooms and conference rooms.120V motorized window shades do not appear to be listed. Do not use until listing can be verified or until listed units can be installed.
5/11/2022TransferCorrect Below* Guest room AC units floors 1 through 3.Labelled to require 15A OCPD.