| Date | Status | Code | Description | Ref | Location | Comments |
| 8/29/2022 | Transfer | Correct Below | * | | | additional items may be present- panel schedules not provided and not all receiving devices/wiring/panel makeup has been completed |
| 8/29/2022 | Transfer | Correct Below | * | | | disconnects required for hardwired appliances |
| 8/29/2022 | Transfer | Correct Below | * | | | need access to rooftop |
| 8/29/2022 | Transfer | Correct Below | * | | | hood controller incomplete |
| 8/29/2022 | Transfer | Correct Below | * | | | panel schedules and bundling required at panels |
| 8/29/2022 | Transfer | Correct Below | * | | | ground fault protection, breakers locks and warning labels required for heat trace circuits |
| 8/29/2022 | Transfer | Correct Below | * | | | receiving area not complete- |
| 8/29/2022 | Transfer | Correct Below | * | | | receptacles miswired at POS and office |
| 8/29/2022 | Transfer | Correct Below | * | | | some emergency lighting units and remote heads are not functioning properly |
| 8/29/2022 | Transfer | Correct Below | * | | | gfci protection required for all kitchen receptacles per NEC 210.8B |
| 8/29/2022 | Transfer | Correct Below | * | | | sign permit required for new Little Caesar's sign |
| 8/29/2022 | Transfer | Correct Below | * | | | Special permission terms for new service are required to be met- shunt trips at each service location, placarding of other service location, additional disconnect at south service, soffit lighting on Little Caesars service etc. |