Inspection #: 711950
Inspection Type: Final Fire Inspection
Inspector: B.Meinhardt
Result: Correction
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/29/2022TransferFire 13Correction(s) #1Please correct the following: C concourse chiller room&nbsp;<div><br></div><div>(1) sprinkler heads blocked by beams/fire proofing/unistrut and conduit&nbsp;</div><div>&nbsp; &nbsp; &nbsp; &nbsp;8/9/2022 Call for reinspection....Bart Meinhardt AFD</div><div>(2) No installers cert provide&nbsp;<div>&nbsp; &nbsp; &nbsp; &nbsp;8/9/2022 item resolved...Bart Meinhardt AFD</div><div>(3) 3rd party Special Inspection of Plumbing, mechanical and electrical components for the clearance to the fire sprinkler system required per 2018 IBC 1705.12.6 #6.<div>&nbsp; &nbsp; &nbsp; &nbsp; 8/9/2022 item resolved...Bart Meinhardt AFD</div><div><br></div></div></div>