Inspection #: 711942
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Partial
Comment: See corrections

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/14/2022TransferCorrect Below* New AHU15 amp max overcurrent protection required for lighting circuit per manufacturer label. Provide plans for inspection, not provided for this inspection. Unable to verify install matches plans. Verify correct circuits are used for equipment and lighting. If alternates are used, provide field change order. Lighting circuit for AHU added to existing circuit 27.
3/29/2022CorrectedCorrect Below* Demonstrate overload setting for 4th floor VFD to RF-1. 
3/29/2022CorrectedCorrect Below* Relocation of circuit to RF-1. Provide field change order for relocation of branch circuit supply.  
3/29/2022CorrectedCorrect Below* AHU replacement incomplete.  