| Date | Status | Code | Description | Ref | Location | Comments |
| 4/29/2022 | Transfer | Fire 13 | Correction(s) #1 | Please correct the following: | | C concourse chiller room <div><br></div><div>(1) sprinkler heads blocked by beams/fire proofing/unistrut and conduit </div><div><br></div><div>(2) No installers cert provide <div><br></div><div>(3) 3rd party Special Inspection of Plumbing, mechanical and electrical components for the clearance to the fire sprinkler system required per 2018 IBC 1705.12.6 #6.<div><br></div><div><br></div></div></div> |