Inspector: M.Green
Result: Correction
Comment: Requested by: Tim Gorham 3506496 tgorham@alcanelectric.com | | Electrical final inspection for the following: *All guest rooms (two minor corrections remaining). *All corridors. *Conference Rooms (one minor correction remaining). AREAS WITH CORRECTIONS REMAINING OR NOT INSPECTED: *BACK OF HOUSE. *KITCHEN / BAR AREAS. *LOBBY. *ROOFTOP. *MICROTURBINES AND CONNECTION TO BUILDING WIRING. *EXTERIOR.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/11/2022TransferCorrect Below* Various guest rooms and conference rooms.120V motorized window shades do not appear to be listed. Do not use until listing can be verified or until listed units can be installed.
5/11/2022TransferCorrect Below* Guest room AC units floors 1 through 3.Labelled to require 15A OCPD.
4/19/2022TransferCorrect Below* Pool.(1) exit and (1) emergency light not working.
4/19/2022TransferCorrect Below* BarReceptacles on both sides of bar, within 6ft of sink not GFCI protected.
4/19/2022TransferCorrect Below* Back of House - Mech Room.1. Label disconnects and VFDs as to load controlled / served. 2. Class 2 wiring inside (2) circ pump disconnects does not have separation from line voltage.
4/19/2022TransferCorrect Below* Back of House - Laundry.Hardwired commercial washers and dryers not installed.
4/19/2022TransferCorrect Below* Back of House - Pantry 157.Walk-in cooler not installed.
4/18/2022TransferCorrect Below* Pool equipment.Verify GFCI protection for equipment - single phase 120V through 240V.
4/15/2022TransferCorrect Below* Receptacle next to Panel C.Dead.
4/15/2022TransferCorrect Below* Panel C.Breaker blanks.
4/15/2022TransferCorrect Below* Back of house restroomEM light not coming on.
4/15/2022TransferCorrect Below* Back of house restrooms.Breaker lock for hand dryers.
4/15/2022CorrectedCorrect Below* Conference Rooms.(1) exit sign not coming on in EM mode.
4/15/2022CorrectedCorrect Below* Conference Rooms.(4) missing recessed can lights.