Date | Status | Code | Description | Ref | Location | Comments |
5/11/2022 | Transfer | Correct Below | * | | Various guest rooms and conference rooms. | 120V motorized window shades do not appear to be listed.
Do not use until listing can be verified or until listed units can be installed. |
5/11/2022 | Transfer | Correct Below | * | | Guest room AC units floors 1 through 3. | Labelled to require 15A OCPD. |
4/19/2022 | Transfer | Correct Below | * | | Pool. | (1) exit and (1) emergency light not working. |
4/19/2022 | Transfer | Correct Below | * | | Bar | Receptacles on both sides of bar, within 6ft of sink not GFCI protected. |
4/19/2022 | Transfer | Correct Below | * | | Back of House - Mech Room. | 1. Label disconnects and VFDs as to load controlled / served. 2. Class 2 wiring inside (2) circ pump disconnects does not have separation from line voltage. |
4/19/2022 | Transfer | Correct Below | * | | Back of House - Laundry. | Hardwired commercial washers and dryers not installed. |
4/19/2022 | Transfer | Correct Below | * | | Back of House - Pantry 157. | Walk-in cooler not installed. |
4/18/2022 | Transfer | Correct Below | * | | Pool equipment. | Verify GFCI protection for equipment - single phase 120V through 240V. |
4/15/2022 | Transfer | Correct Below | * | | Receptacle next to Panel C. | Dead. |
4/15/2022 | Transfer | Correct Below | * | | Panel C. | Breaker blanks. |
4/15/2022 | Transfer | Correct Below | * | | Back of house restroom | EM light not coming on. |
4/15/2022 | Transfer | Correct Below | * | | Back of house restrooms. | Breaker lock for hand dryers. |
4/15/2022 | Corrected | Correct Below | * | | Conference Rooms. | (1) exit sign not coming on in EM mode. |
4/15/2022 | Corrected | Correct Below | * | | Conference Rooms. | (4) missing recessed can lights. |