Inspection #: 709867
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Approved
Comment: Corrections made. Electrical final approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/11/2022CorrectedCorrect Below* Various equipment throughout.Disconnects required per 422.30 and 31. Disconnect remains incomplete at ice maker. Chapter 3 wiring method replaced with cord connection. Instructions do not allow for cord connection of equipment. Fixed wiring method required.
3/11/2022CorrectedCorrect Below* Rear ceiling Heat trace incomplete. Update to correction: Ground fault protection for equipment required. Disconnect required to be lockable. See 427.22 and 427.55. Identification of heat tracing in pipeline required per 427.13. Update to correction: Breaker lock required. Lockable device required to remain in place with lock removed.