Inspection #: 709695
Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: Requested by: Tim Gorham 3506496 tgorham@alcanelectric.com | | Conditional electrical final approved until 5/20/2022 to permit hotel personnel to begin set-up only. Inspection today covered Bar, Kitchen, Lobby power. Outstanding corrections remain to be resolved from inspections dated 3/25/2022 through 4/19/2022. Kitchen equipment not on site. Equipment connections all safed-off at locations where equipment not installed. Possible issues with micro turbine remain.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/13/2022TransferCorrect Below* 4th floor ceiling mounted exit outside 429, 432.Not coming on with other exits when power shut off.
4/13/2022TransferCorrect Below* 3rd floor by west end stair.Exit not coming on with other exits in the area when power shut off.
4/13/2022TransferCorrect Below* 2nd floor, by east stairway.Low mounted exit sign broken.
4/11/2022TransferCorrect Below* Several showers such as 242, 113, 114.Will require shower curtains.
4/11/2022TransferCorrect Below* Room AC units.Require 15A OCPD.