Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 709385
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Partial
Comment: Electrical final conditionally approved for extension until 4/22/22.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/11/2022TransferCorrect Below* Various equipment throughout.Disconnects required per 422.30 and 31. Disconnect remains incomplete at ice maker. Chapter 3 wiring method replaced with cord connection. Instructions do not allow for cord connection of equipment. Fixed wiring method required.
3/11/2022CorrectedCorrect Below* Unit heater. Incomplete. If not to be installed, provide Field change order to remove from plans. Update to correction: Provide for onsite inspection. Plans not provided. Have changes been made to electrical plans related to permit? Update with field change order or other as necessary.
3/11/2022TransferCorrect Below* Rear ceiling Heat trace incomplete. Update to correction: Ground fault protection for equipment required. Disconnect required to be lockable. See 427.22 and 427.55. Identification of heat tracing in pipeline required per 427.13. Update to correction: Breaker lock required. Lockable device required to remain in place with lock removed.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter