Date | Status | Code | Description | Ref | Location | Comments |
4/11/2022 | Transfer | Correct Below | * | | Room 120. | Receptacles missing trim. |
4/11/2022 | Transfer | Correct Below | * | | Rooms 103, 118, 119, 104, 120. | Configured with (2) receptacles in entry by shower. The top receptacle is GFCI protected. The lower receptacle in not GFCI protected. Will need to see vanities installed. |
4/11/2022 | Transfer | Correct Below | * | | Room 245 | Double duplex receptacle above AC unit does not fit tight to wall. |
4/11/2022 | Transfer | Correct Below | * | | Room 108 | Receptacles dead: *By AC unit. *Duplex by night stand. *GFCI by shower. |
4/11/2022 | Transfer | Correct Below | * | | Several showers such as 242, 113, 114. | Will require shower curtains. |
4/11/2022 | Transfer | Correct Below | * | | Room AC units. | Require 15A OCPD. |
4/11/2022 | Transfer | Correct Below | * | | "Floating night stands" | Will need to verify hidden listing mark. |
4/11/2022 | Transfer | Correct Below | * | | 2nd floor guest rooms, receptacles by showers. | Receptacles are within 6ft of vanity sink. GFCI protection required. Some other configurations with other receptacles within 6ft of sink such as 242. |
4/8/2022 | Transfer | Correct Below | * | | 3rd and 4th floor "floating night stand." | No listing mark on the product. |
4/8/2022 | Transfer | Correct Below | * | | Room 342. | Not complete - room has been used as a staging area. |