Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 708728
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Requested by: Tim Gorham 907-360-6496 Tgorham@alcanelectric.com | | Partial progress electrical final for 2nd floor guest rooms 240-251, and 1st floor guest rooms 102-122.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/11/2022TransferCorrect Below* Room 120.Receptacles missing trim.
4/11/2022TransferCorrect Below* Rooms 103, 118, 119, 104, 120.Configured with (2) receptacles in entry by shower. The top receptacle is GFCI protected. The lower receptacle in not GFCI protected. Will need to see vanities installed.
4/11/2022TransferCorrect Below* Room 245Double duplex receptacle above AC unit does not fit tight to wall.
4/11/2022TransferCorrect Below* Room 108Receptacles dead: *By AC unit. *Duplex by night stand. *GFCI by shower.
4/11/2022TransferCorrect Below* Several showers such as 242, 113, 114.Will require shower curtains.
4/11/2022TransferCorrect Below* Room AC units.Require 15A OCPD.
4/11/2022TransferCorrect Below* "Floating night stands"Will need to verify hidden listing mark.
4/11/2022TransferCorrect Below* 2nd floor guest rooms, receptacles by showers.Receptacles are within 6ft of vanity sink. GFCI protection required. Some other configurations with other receptacles within 6ft of sink such as 242.
4/8/2022TransferCorrect Below* 3rd and 4th floor "floating night stand."No listing mark on the product.
4/8/2022TransferCorrect Below* Room 342.Not complete - room has been used as a staging area.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter