Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 708727
Inspection Type: Electrical Rough
Inspector: E.Widman
Result: Progress
Comment: Progress inspection for C4655,C4630, C4678, and C4781.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/11/2022Transfer01See inspection comments Motor controllers throughoutDemonstrate motor overload settings per manufacturer instructions and part III of 430.
4/11/2022Transfer01See inspection comments Ch-3.Access and working clearances required.
4/11/2022Transfer01See inspection comments Pull box above 84NDP-HBPull box entries required to be per 314.28
4/8/2022Transfer01See inspection comments Spare conduits.Plug spare conduits associated with project.
4/8/2022Transfer01See inspection comments VFD's-C0147AProvide access to inspect interior and manufacturer labels. Per instructions-interior labels state max overcurrent protection for units. Demonstrate overload settings for all motors and set per 430.32 and motor branch circuit short circuit and ground fault protection per 430.52. Can verify at next inspection comparing with VFD overcurrent protection.
4/8/2022Transfer01See inspection comments Compressor disconnects. labels required. Label per sheet notes and being part of a tested series combination. Plans require fuses to be installed to limit fault current to less than 10,000. Label per 110.22 (C).
4/8/2022Transfer01See inspection comments C0147A compressorsAccess and working clearances per 110.26 required at disconnects and associated equipment.
4/8/2022Transfer01See inspection comments Plans-room C0147AProvide change order for alternate method of connection to compressor equipment.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS