Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 707692
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Partial
Comment: Inspection for main corridor ceiling in front of TI. Correction made for ceiling location at corridor. Other corrections remain.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/1/2022CorrectedCorrect Below* Common area, corridorInspection for corridor area. Common area work on plans was noted as incomplete on previous inspection. No record of electrical rough inspection for this area. New lighting types G and F2 at common area (corridor) ceiling covered without inspection. Provide access to effectively inspect wiring to new lights above ceiling. Depending on location of boxes or other wiring methods above ceiling, access panels or additional inspection access locations may be required.
3/11/2022TransferCorrect Below* Various equipment throughout.Disconnects required per 422.30 and 31.
3/11/2022TransferCorrect Below* Unit heater. Incomplete. If not to be installed, provide Field change order to remove from plans. Update to correction: Provide for onsite inspection. Plans not provided. Have changes been made to electrical plans related to permit? Update with field change order or other as necessary.
3/11/2022TransferCorrect Below* Rear ceiling Heat trace incomplete. Update to correction: Ground fault protection for equipment required. Disconnect required to be lockable. See 427.22 and 427.55. Identification of heat tracing in pipeline required per 427.13.
3/11/2022CorrectedCorrect Below* Common area work on plans incomplete.  
3/11/2022CorrectedCorrect Below* Water heater installation manualRequired overcurrent device-65 amp.