| Date | Status | Code | Description | Ref | Location | Comments |
| 5/20/2022 | Transfer | EC1 | Correct Below | | Above suspended ceiling. | Close open box at southeast corner of office space. |
| 5/20/2022 | Transfer | EC1 | Correct Below | | Support metal flex off of ceiling grid. | |
| 5/20/2022 | Transfer | EC1 | Correct Below | | Fasten lights to grid. Lights not currently fastened. | |
| 5/20/2022 | Transfer | EC1 | Correct Below | | Various locations. | All existing cables and raceways required to be properly supported. Raceways appear to be going to upper level. Cap/plug spare raceways if connected to power wiring system. Low volt cables required to be supported off of grid, if not used, demo cables or mark as spare or for intended use. Boxes required to have KO seals where open holes in boxes exist. |