Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 705737
Inspection Type: Ceiling Rough Electrical
Inspector: E.Widman
Result: Correction
Comment: Ceiling inspection See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/20/2022TransferEC1Correct Below Above suspended ceiling. Close open box at southeast corner of office space.
5/20/2022TransferEC1Correct Below Support metal flex off of ceiling grid.  
5/20/2022TransferEC1Correct Below Fasten lights to grid. Lights not currently fastened.  
5/20/2022TransferEC1Correct Below Various locations. All existing cables and raceways required to be properly supported. Raceways appear to be going to upper level. Cap/plug spare raceways if connected to power wiring system. Low volt cables required to be supported off of grid, if not used, demo cables or mark as spare or for intended use. Boxes required to have KO seals where open holes in boxes exist.