Inspection #: 705527
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: Correction remains from previous inspection. Utilization equipment fastened in place (instahots) are combined on circuit with other utilization equipment not fastened in place (refrigerators). Instahots are over max allowed (50%) for connection to other equipment not fastened in place on the same circuit. See 210.23 (A)(2) for utilization equipment fastened in place. Provide Field change order for branch circuit modifications for equipment supplied.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/16/2022TransferCorrect Below*  Verify branch circuit rating for cord connected equipment fastened in place and other equipment not fastened in place meets 210.23 (A)(2). Instahot (fixed appliance, fastened in place) appears to be connected to circuit with other equipment not fastened in place. Instahot rating is 11.3 amp. If eliminated or circuits rearranged, update panel schedule to match asbuilt. Depending on final configuration, provide field change order for changes as necessary to update and revise plans.