| Date | Status | Code | Description | Ref | Location | Comments |
| 3/22/2022 | Transfer | Correct Below | * | | carrs | update panel schedules throughout |
| 3/22/2022 | Transfer | Correct Below | * | | carrs | additional disconnects required on cooler units at front and rear west of store |
| 3/14/2022 | Corrected | Correct Below | * | | carrs | areas not inspected yet |
| 3/14/2022 | Transfer | Correct Below | * | | customer service | remove iso ground receptacles |
| 3/14/2022 | Corrected | Correct Below | * | | starbucks | update panel schedule |
| 3/14/2022 | Corrected | Correct Below | * | | customer service | update panel schedule |
| 3/14/2022 | Corrected | Correct Below | * | | starbucks | track lighting requires seismic wiring every 4 feet |
| 3/14/2022 | Corrected | Correct Below | * | | starbucks | close all junction boxes |
| 3/14/2022 | Corrected | Correct Below | * | | starbucks | can lights req 2 seismic wires on opposite corners and 4 screws for spanner brackets |
| 3/14/2022 | Corrected | Correct Below | * | | oaken keg | possibly other items without panel schedule |
| 3/14/2022 | Corrected | Correct Below | * | | oaken keg | disconnects required on each cooler unit- must be grouped |
| 3/14/2022 | Corrected | Correct Below | * | | oaken keg | where is nameplate on coolers? need to verify UL listing and amperage/voltage ratings for overcurrent protection |
| 3/14/2022 | Transfer | Correct Below | * | | oaken keg | seismic wires req at every 4' of track lighting |
| 3/14/2022 | Transfer | Correct Below | * | | oaken keg | close all junction boxes |
| 3/14/2022 | Corrected | Correct Below | * | | oaken keg | label neutrals with circuit numbers |
| 3/14/2022 | Corrected | Correct Below | * | | oaken keg | panel requires ko seals |
| 3/14/2022 | Corrected | Correct Below | * | | oaken keg | updated panel schedule required |
| 3/14/2022 | Corrected | Correct Below | * | | oaken keg | label panel with source |