Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 705227
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Correction
Comment: Please contact Colton in route at (907) 315-3343 for final inspection. Requested by: Tony Noethlich (907) 336-1258 tn@sei-ak.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/22/2022TransferCorrect Below* carrsupdate panel schedules throughout
3/22/2022TransferCorrect Below* carrsadditional disconnects required on cooler units at front and rear west of store
3/14/2022CorrectedCorrect Below* carrsareas not inspected yet
3/14/2022TransferCorrect Below* customer serviceremove iso ground receptacles
3/14/2022CorrectedCorrect Below* starbucksupdate panel schedule
3/14/2022CorrectedCorrect Below* customer serviceupdate panel schedule
3/14/2022CorrectedCorrect Below* starbuckstrack lighting requires seismic wiring every 4 feet
3/14/2022CorrectedCorrect Below* starbucksclose all junction boxes
3/14/2022CorrectedCorrect Below* starbuckscan lights req 2 seismic wires on opposite corners and 4 screws for spanner brackets
3/14/2022CorrectedCorrect Below* oaken kegpossibly other items without panel schedule
3/14/2022CorrectedCorrect Below* oaken kegdisconnects required on each cooler unit- must be grouped
3/14/2022CorrectedCorrect Below* oaken kegwhere is nameplate on coolers? need to verify UL listing and amperage/voltage ratings for overcurrent protection
3/14/2022TransferCorrect Below* oaken kegseismic wires req at every 4' of track lighting
3/14/2022TransferCorrect Below* oaken kegclose all junction boxes
3/14/2022CorrectedCorrect Below* oaken keglabel neutrals with circuit numbers
3/14/2022CorrectedCorrect Below* oaken kegpanel requires ko seals
3/14/2022CorrectedCorrect Below* oaken kegupdated panel schedule required
3/14/2022CorrectedCorrect Below* oaken keglabel panel with source
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS