Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 705214
Inspection Type: Electrical Rough
Inspector: O.Burbridge
Result: Partial
Comment: corrections made- electrical rough in approved

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/14/2022Corrected01See inspection comments Hall 3 way switchSeparation required between power and low voltage class 2 required. Install per 725.136. Separation not provided.
3/14/2022Corrected01See inspection comments Exam rooms-light switch locations. Wiring method approved for use as grounding and bonding means required.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS