Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 705082
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: Corrections remain from previous inspection. Electrical final conditionally approved for use of space until 4/15/22. Inspection for corridor area. Common area work on plans was noted as incomplete on previous inspection. New lighting types G and F2 at common area (corridor) ceiling covered without inspection. Provide access to effectively inspect wiring to new lights above ceiling. Depending on location of boxes above ceiling, access panels may be required.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/1/2022TransferCorrect Below* Common area, corridorInspection for corridor area. Common area work on plans was noted as incomplete on previous inspection. No record of electrical rough inspection for this area. New lighting types G and F2 at common area (corridor) ceiling covered without inspection. Provide access to effectively inspect wiring to new lights above ceiling. Depending on location of boxes or other wiring methods above ceiling, access panels or additional inspection access locations may be required. Multiple electrical contractors noted on permit.
3/11/2022TransferCorrect Below* Various equipment throughout.Disconnects required per 422.30 and 31.
3/11/2022TransferCorrect Below* Unit heater. Incomplete. If not to be installed, provide Field change order to remove from plans.
3/11/2022CorrectedCorrect Below* Various equipment. Cord connection with attachment plug required. Cord not suitable for fixed wiring method.
3/11/2022TransferCorrect Below* Rear ceiling Heat trace incomplete.
3/11/2022TransferCorrect Below* Common area work on plans incomplete.  
3/11/2022TransferCorrect Below* Water heater installation manualRequired overcurrent device-65 amp.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter