Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 704331
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Correction
Comment: Final inspection for 2nd floor Requested by: Tim Gorham 907-350-6496 Tgorham@alcanelectric.com | | 2nd floor guest rooms 202 - 238. Partial electrical final inspection. Rooms 212 and 214 have a different shower / toilet configuration. These rooms will require a shower curtain or door. Corrections as below.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/8/2022Transfer01See inspection comments Powered curtains.Will need to check for listings ,etc.
4/8/2022Transfer01See inspection comments "Floating nightstands"No listing mark on product.
4/8/2022Transfer01See inspection comments Room AC units.Require 15A breaker max.
4/8/2022Transfer01See inspection comments Room 219Receptacle trim plates by AC unit.
4/8/2022Transfer01See inspection comments Room 202Switch for globe-type sconce not installed.
1/26/2022Transfer01See inspection comments Conference room bathroom-southVerify access is provided for fan control/louver at ceiling location. Ceiling access planned.
10/25/2021Transfer01See inspection comments Microturbine-one line diagram, separately derived system. Grounding electrode conductor required.
10/25/2021Transfer01See inspection comments Service, microturbineVerify microturbine configuration with utility. Verify disconnecting means and requirement for having lockable disconnect. Labeling required for alternate source per 702.
10/25/2021Transfer01See inspection comments Service.Label AFC and date calculated.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter