Inspection #: 703210
Inspection Type: Mechanical Rough
Inspector: E.Huckaba
Result: Partial
Comment: Flexes, diffusers and EA grilles for Back Of House Area and SA flexes and diffusers ONLY in Conference Room- APPROVED. NOTES: OK TO DROP LID. RA NOT COMPLETE IN CONFERENCE ROOM.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/21/2022TransferMechRghSee commentsSee Inspector CommentsLOWER ROOF PER 2018 IMC- SECTION 306.5- EQUIPMENT OR APPLIANCES ON ROOFS OR ELEVATED STRUCTURES- WHERE APPLIANCES ARE LOCATED ON ROOFS OR ELEVATED STRUCTURES WHERE PERSONEL WOULD CLIMB HIGHER THAN 16 FEET ABOVE GRADE, AN INTERIOR OR EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED.