Inspection #: 702659
Inspection Type: Electrical Rough
Inspector: E.Widman
Result: Correction
Comment: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/14/2022Transfer01See inspection comments Hall 3 way switchSeparation required between power and low voltage class 2 required. Install per 725.136. Separation not provided.
3/14/2022Transfer01See inspection comments Exam rooms-light switch locations. Wiring method approved for use as grounding and bonding means required.