| Date | Status | Code | Description | Ref | Location | Comments |
| 2/16/2022 | Transfer | EC1 | Correct Below | | Ceiling paddle fan. | Discussed planned connection of ceiling fan. Required to be connected with a chapter 3 wiring method approved for the location. Flexible cord not permitted to be concealed by suspended ceiling. See 400.12 (5), uses not permitted. |
| 2/16/2022 | Transfer | EC1 | Correct Below | | 4th floor VFD at elevator lobby | Working clearances and access required for VFD per 110.26. Currently installed above suspended ceiling. Unless Required to be installed at this location based on install instructions or function. See limited access 110.26 (A)(4). If so, provide this documentation. |
| 2/16/2022 | Transfer | EC1 | Correct Below | | Elevator lobbies | Temp lighting remains connected through elevator lobby ceilings, will need to be removed and inspected when lighting can be removed. Cord not a suitable wiring method above suspended ceiling. |