Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 702258
Inspection Type: Ceiling Rough Electrical
Inspector: E.Widman
Result: Partial
Comment: Electrical ceiling rough inspection approved for escalator landing 425.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/16/2022TransferEC1Correct Below Ceiling paddle fan. Discussed planned connection of ceiling fan. Required to be connected with a chapter 3 wiring method approved for the location. Flexible cord not permitted to be concealed by suspended ceiling. See 400.12 (5), uses not permitted.
2/16/2022TransferEC1Correct Below 4th floor VFD at elevator lobbyWorking clearances and access required for VFD per 110.26. Currently installed above suspended ceiling. Unless Required to be installed at this location based on install instructions or function. See limited access 110.26 (A)(4). If so, provide this documentation.
2/16/2022TransferEC1Correct Below Elevator lobbiesTemp lighting remains connected through elevator lobby ceilings, will need to be removed and inspected when lighting can be removed. Cord not a suitable wiring method above suspended ceiling.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS