Inspection #: 702066
Inspection Type: Ceiling Rough Electrical
Inspector: E.Widman
Result: Partial
Comment: Electrical ceiling rough approved for elevator lobbies 125, 230, 330. Temp lighting remains connected through elevator lobby ceilings, will need to be removed and inspected when lighting can be removed. Discussed issues that may arise at 4th floor, work incomplete at 4th floor location.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/16/2022TransferEC1Correct Below Ceiling paddle fan. Discussed planned connection of ceiling fan. Required to be connected with a chapter 3 wiring method approved for the location. Flexible cord not permitted to be concealed by suspended ceiling. See 400.12 (5), uses not permitted.
2/16/2022TransferEC1Correct Below 4th floor VFD at elevator lobbyWorking clearances and access required for VFD per 110.26. Currently installed above suspended ceiling. Unless Required to be installed at this location based on install instructions or function. See limited access 110.26 (A)(4). If so, provide this documentation.
2/16/2022TransferEC1Correct Below Elevator lobbiesTemp lighting remains connected through elevator lobby ceilings, will need to be removed and inspected when lighting can be removed. Cord not a suitable wiring method above suspended ceiling.