Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 701305
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Partial
Comment: Electrical final conditionally approved for move in until 3/25/22. See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/11/2022TransferCorrect Below* Various equipment throughout.Disconnects required per 422.30 and 31.
3/11/2022TransferCorrect Below* Unit heater. Incomplete. If not to be installed, provide Field change order to remove from plans.
3/11/2022TransferCorrect Below* Various equipment. Cord connection with attachment plug required. Cord not suitable for fixed wiring method.
3/11/2022TransferCorrect Below* Rear ceiling Heat trace incomplete.
3/11/2022TransferCorrect Below* Common area work on plans incomplete.  
3/11/2022TransferCorrect Below* Water heater installation manualRequired overcurrent device-65 amp.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS