Inspection #: 701261
Inspection Type: Ceiling Rough Electrical
Inspector: E.Widman
Result: Partial
Comment: Ceiling rough approved for vestibule 226, and 326. Escalator lobby 125 upper ceiling. Correction remains for VFD.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/25/2022TransferEC1Correct Below  Working clearances and access required for VFD per 110.26. Currently installed above suspended ceiling. Unless Required to be installed at this location based on install instructions or function. See limited access 110.26 (A)(4). If so, provide this documentation.