Inspection #: 698975
Inspection Type: Electrical Rough
Inspector: E.Widman
Result: Partial
Comment: Electrical ceiling rough for rooms 226 through 251 approved. Conference room bathrooms ceiling rough approved. Corridor 127 ceiling rough approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/26/2022Transfer01See inspection comments Conference room bathroom-southVerify access is provided for fan control/louver at ceiling location. Ceiling access planned.
10/25/2021Transfer01See inspection comments Microturbine-one line diagram, separately derived system. Grounding electrode conductor required.
10/25/2021Transfer01See inspection comments Service, microturbineVerify microturbine configuration with utility. Verify disconnecting means and requirement for having lockable disconnect. Labeling required for alternate source per 702.
10/25/2021Transfer01See inspection comments Service.Label AFC and date calculated.