Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 696269
Inspection Type: Electrical Rough
Inspector: V.Fosberg
Result: Partial
Comment: rooms 430 to 451 all east half of 4th floor ceilings and drop lids, hallways and elevator lobby. also electrical rough in for pool room, pool mechanical room, pool electrical room and conference storage room. Electrical approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/25/2021Transfer01See inspection comments Microturbine-one line diagram, separately derived system. Grounding electrode conductor required.
10/25/2021Transfer01See inspection comments Service, microturbineVerify microturbine configuration with utility. Verify disconnecting means and requirement for having lockable disconnect. Labeling required for alternate source per 702.
10/25/2021Transfer01See inspection comments Service.Label AFC and date calculated.
10/22/2021Corrected01See inspection comments Location of branch circuit panel in pool equipment room. Drawings show panel in pool equipment room. panel put in separate room from pool equipment.2017 680.14(A) defines a pool equipment room as a corrosive environment and requires specific wiring methods. The pool room itself is also a corrosive environment. The panel will have to be isolated from corrosive atmospheres.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter