Inspection #: 695302
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Partial
Comment: Requested by: Tim Gorham 3506496 tgorham@alcanelectric.com | | Corridor 156 above sheetrock ceiling electrical rough approved. Also, Receptacle added in southwest corner of Conference Room.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/10/2021Corrected01See inspection comments Conference room(s) southeast corner.Requires receptacle to meet proper spacing for 6ft-12ft rule.
10/25/2021Transfer01See inspection comments Microturbine-one line diagram, separately derived system. Grounding electrode conductor required.
10/25/2021Transfer01See inspection comments Service, microturbineVerify microturbine configuration with utility. Verify disconnecting means and requirement for having lockable disconnect. Labeling required for alternate source per 702.
10/25/2021Transfer01See inspection comments Service.Label AFC and date calculated.
10/22/2021Transfer01See inspection comments Location of branch circuit panel in pool equipment room. Drawings show panel in pool equipment room.2017 680.14(A) defines a pool equipment room as a corrosive environment and requires specific wiring methods. The pool room itself is also a corrosive environment. The panel will have to be isolated from corrosive atmospheres.