Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 693709
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Correction
Comment: Requested by: Tim Gorham 3506496 tgorham@alcanelectric.com | | *1st floor framed-down ceilings. Electrical rough approved. *Corridor between pool and conference room walls and above sheetrock ceilings. Electrical rough approved. *Public restrooms by conference room. Electrical rough approved. *Lobby center strip that lines up with and extends into corridor. Electrical rough above ceiling approved. *Conference room(s). Electrical rough approved except as below.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/10/2021Transfer01See inspection comments Conference room(s) southeast corner.Requires receptacle to meet proper spacing for 6ft-12ft rule.
10/25/2021Transfer01See inspection comments Microturbine-one line diagram, separately derived system. Grounding electrode conductor required.
10/25/2021Transfer01See inspection comments Service, microturbineVerify microturbine configuration with utility. Verify disconnecting means and requirement for having lockable disconnect. Labeling required for alternate source per 702.
10/25/2021Transfer01See inspection comments Service.Label AFC and date calculated.
10/22/2021Transfer01See inspection comments Location of branch circuit panel in pool equipment room. Drawings show panel in pool equipment room.2017 680.14(A) defines a pool equipment room as a corrosive environment and requires specific wiring methods. The pool room itself is also a corrosive environment. The panel will have to be isolated from corrosive atmospheres.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter