| Date | Status | Code | Description | Ref | Location | Comments |
| 4/8/2022 | Transfer | 01 | See inspection comments | | Spare conduits. | Plug spare conduits associated with project. |
| 4/8/2022 | Transfer | 01 | See inspection comments | | VFD's-C0147A | Provide access to inspect interior and manufacturer labels. Per instructions-interior labels state max overcurrent protection for units. Demonstrate overload settings for all motors and set per 430.32 and motor branch circuit short circuit and ground fault protection per 430.52. Can verify at next inspection comparing with VFD overcurrent protection. |
| 4/8/2022 | Transfer | 01 | See inspection comments | | Compressor disconnects. | labels required. Label per sheet notes and being part of a tested series combination. Plans require fuses to be installed to limit fault current to less than 10,000. Label per 110.22 (C). |
| 4/8/2022 | Transfer | 01 | See inspection comments | | C0147A compressors | Access and working clearances per 110.26 required at disconnects and associated equipment. |
| 4/8/2022 | Transfer | 01 | See inspection comments | | Plans-room C0147A | Provide change order for alternate method of connection to compressor equipment. |