Date | Status | Code | Description | Ref | Location | Comments |
11/22/2021 | | 01 | See inspection comments | | Corridor ceiling cloud outside guest room 222. | Remote, low voltage power supply for exterior lights not installed. Access hatch not framed-in. |
11/22/2021 | | 01 | See inspection comments | | Guest room 224 bathroom. | Ceiling not framed. |
10/25/2021 | Transfer | 01 | See inspection comments | | Microturbine-one line diagram, separately derived system. | Grounding electrode conductor required. |
10/25/2021 | Transfer | 01 | See inspection comments | | Service, microturbine | Verify microturbine configuration with utility. Verify disconnecting means and requirement for having lockable disconnect. Labeling required for alternate source per 702. |
10/25/2021 | Transfer | 01 | See inspection comments | | Service. | Label AFC and date calculated. |
10/22/2021 | Transfer | 01 | See inspection comments | | Location of branch circuit panel in pool equipment room. Drawings show panel in pool equipment room. | 2017 680.14(A) defines a pool equipment room as a corrosive environment and requires specific wiring methods. The pool room itself is also a corrosive environment. The panel will have to be isolated from corrosive atmospheres. |