Inspection #: 692137
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Partial
Comment: Requested by: Tim Gorham 3506496 tgorham@alcanelectric.com | | 2nd floor guest rooms 201 - 228. Framed-down ceilings electrical rough approved except as below. 2nd floor corridor ceiling clouds from outside 201 - 222. Electrical rough approved except as below.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
11/22/2021 01See inspection comments Corridor ceiling cloud outside guest room 222.Remote, low voltage power supply for exterior lights not installed. Access hatch not framed-in.
11/22/2021 01See inspection comments Guest room 224 bathroom.Ceiling not framed.
10/25/2021Transfer01See inspection comments Microturbine-one line diagram, separately derived system. Grounding electrode conductor required.
10/25/2021Transfer01See inspection comments Service, microturbineVerify microturbine configuration with utility. Verify disconnecting means and requirement for having lockable disconnect. Labeling required for alternate source per 702.
10/25/2021Transfer01See inspection comments Service.Label AFC and date calculated.
10/22/2021Transfer01See inspection comments Location of branch circuit panel in pool equipment room. Drawings show panel in pool equipment room.2017 680.14(A) defines a pool equipment room as a corrosive environment and requires specific wiring methods. The pool room itself is also a corrosive environment. The panel will have to be isolated from corrosive atmospheres.